Skip to content
Secured Engineers Pvt. Ltd. logo
Home
Company Insights Resources Locations & project coverage About Founder — Er. Ankur Kaplesh
Services Mechanical / HVACElectricalPlumbingFire ProtectionLow Voltage / ELVSolar EPCMEP Consultancy & ApprovalsAMC / MaintenanceTurnkey EPCFire NOC AssistanceCEIG Liaison & EnergisationTesting & Commissioning AI Video Analytics
Industries Manufacturing & IndustrialHealthcare & HospitalsHospitality & HotelsWarehousing & LogisticsGovernment & DefenceEducation & InstitutionsData CentrePharmaceutical & CleanroomCold StorageTextile & ApparelAutomobile & Auto-ComponentsFood Processing & FMCGChemical & Process Industries
Free Tools ★ Architect & Design Resource Hub All 56 calculators Solar Financial Calculator Fire Water Storage Checker Fire Pump Room Calculator AC Tonnage Calculator DG Load Calculator MEPF Budget Calculator
Projects Work With Us Get a Free Quote
Design & Coordination

MEP Design for a Hospital: NABH, Medical Gases, Isolation and Power Redundancy

22 October 2026 · 5 min read · by

Title card reading MEP Design for a Hospital: NABH, Medical Gases, Isolation and Power Redundancy, with a hospital floor plan and service risers in outline.
Title card. Not a photograph of a Secured Engineers site.

MEP design for a hospital starts with the clinical brief, then sets design conditions department by department. Operation theatres, ICUs and isolation rooms need controlled air, medical gases need a primary and an alternate source, and life-saving equipment needs uninterrupted power. The 2026 building standards add fire compartments and refuge provisions. NABH is an accreditation, so the national standards and your clinical planner supply the numbers.

What does the design basis look like department by department?

The Indian Public Health Standards (IPHS) 2022 for sub-district and district hospitals are the most explicit government source for room conditions. They are written for public facilities, so use them as a benchmark rather than a mandate for a private hospital. The table gathers the conditions that drive HVAC, gas and power sizing.

AreaAir and room conditions (IPHS 2022)Services and fire notes
Operation theatreAbout 21 °C plus or minus 3, relative humidity 50 to 60%; ideally 20 air exchanges an hour, four of them fresh; laminar flow; differential pressure and HEPA validation monitoredPiped gases and suction per the surgical brief; 120-minute fire and smoke separation from adjoining areas (2026 standards)
ICU and HDUAbout 23 °C plus or minus 2, relative humidity 45 to 65%; 10 to 12 air changes an hour with 4 to 5 fresh; positive pressure; air handling running 24 x 7 with fine filtersPiped gas and suction at each bed; uninterrupted power; 2.0 m door width where beds are evacuated on the bed
Isolation roomSeparate from general wards; negative air pressure; at least six air changes an hourExhaust arrangement and anteroom set by the infection control assessment
Medical gas plantPipeline system expected above 50 beds; oxygen from a tank or generation plant; cylinder manifold as alternate and emergency sourceSeamless copper pipe with brazed joints; colour-coded delivery points; a trained team to monitor pressures
Patient corridors and exitsAisles through which patients are moved at least 2.4 m wide, and exits at least 2.0 m (2026 standards)Space for MEP risers and fire doors with hold-open devices tied to the alarm

How do NABH and the codes fit together?

Three documents carry most of the weight. IPHS 2022 gives room conditions and the medical gas pipeline approach. The DGHS Hospital Manual of April 2025 asks for centralised piped medical gases including oxygen and central suction in theatres, alternate sources of gas that are checked at intervals, an identified isolation room with appropriate environmental controls in intensive care, and monitoring of theatre temperature, humidity and air circulation. The National Building Construction Standards 2026, Part F, cover fire and life safety for hospitals, which the services must be designed around.

NABH is separate. It accredits hospitals against standards it publishes, and we have not reproduced its clauses here. Use the government standards for the numbers, then check the NABH edition current at your application date for the processes the services must support, such as infection control, emergency power and gas supply continuity. Your fire approval, Electrical Inspector sanction and pollution board consents sit alongside; our design and approvals page describes how we coordinate them.

What does the medical gas system need?

IPHS describes the pipeline as a way of delivering medical and anaesthetic gases, vacuum and compressed air from the source to a terminal unit at the point of use. Oxygen comes from a storage tank or a generation plant using pressure swing adsorption technology. The design decisions are:

  • Primary source and alternate. The cylinder manifold acts as the alternate and emergency source if the generation plant or tank fails, and the Hospital Manual asks that alternate sources be checked regularly.
  • Manifold room. A defined area, cool and clean, built of fire-resistant materials with non-conductive flooring and adequate ventilation, with separate places for full and empty cylinders.
  • Pipework and outlets. Seamless copper with flux-less silver brazing, and delivery points colour-coded to the referenced international conventions.
  • Routing. Dedicated shafts. The 2026 standards ask for a dedicated, separate shaft for medical gas pipelines, utility services and electrical services on hospital refuge terraces, and the same discipline helps everywhere.
  • Zoning and monitoring. Alarms and pressure monitoring by area, so a fault in one wing does not become a hospital-wide event.

How should power continuity be designed?

IPHS asks for uninterrupted electric supply in the theatre and critical care units, voltage regulation against fluctuation, and a monitored neutral-to-earth voltage that should not exceed 5 volts. The 2026 building standards go further for tall hospitals: refuge terraces serving patients on ventilators need medical gas, a separate electrical shaft and dedicated UPS and DG back-up for life-saving equipment. A workable design is built in layers:

  • Two independent utility sources where the DISCOM can provide them, with automatic changeover.
  • A DG plant sized for essential loads, with fuel storage and a tested start sequence.
  • UPS for the loads that cannot tolerate even the changeover gap, typically theatres, ICU monitoring and critical IT.
  • Separate essential and non-essential distribution boards, so load shedding is by design rather than by trip.
  • Isolated power arrangements and earthing in theatres and critical care, to the medical-location electrical standard your consultant applies.

The sizing sequence matters: the clinical list of life-saving equipment comes first, then the load schedule, then the DG and UPS ratings. Starting from a DG rating and working back risks putting critical loads on the wrong board.

Where do MEP and fire safety meet?

The 2026 standards require progressive horizontal evacuation in hospitals: patients move through a fire-resistant wall into an adjoining compartment at the same level, and each compartment must hold its own patients and those from the adjoining one. Compartment doors close automatically and are held open electromagnetically. That sets the MEP agenda. Fire doors need alarm-linked hold-open power, ducts and pipes crossing compartment walls need fire-rated penetrations, and a positive-pressure theatre must coexist with a smoke control strategy. Our MEPF cost calculator is a first-pass check on scope, and the fire fighting systems page covers the suppression side.

How Secured Engineers helps

MEP design for healthcare is a coordination exercise, and we run it in-house: HVAC, electrical, plumbing and fire design are produced by one team, so shafts, plant rooms and ceiling voids are resolved on the same drawings. Fire NOC and CEIG filings are prepared in-house, and MEPF and solar can sit under one contract. We work from offices in Noida (Delhi NCR) and Ludhiana, across 535+ projects in 18+ states, with 89.77% repeat clients.

If you already have a hospital design from an architect or another consultant, send it for a technical review: we will check the departmental design basis, gas arrangement, power layers and fire interfaces and list the gaps. Open the design and approvals service, then message us on WhatsApp, call +91 70099 85817, or request a free proposal.

Frequently asked

How many air changes does an operation theatre need?

The Indian Public Health Standards 2022 for district hospitals say ideally 20 air exchanges an hour, of which four are fresh air, with 21 plus or minus 3 degrees Celsius and 50 to 60 percent relative humidity, laminar flow and monitoring of differential pressure and HEPA validation. Treat these as the public-sector benchmark and confirm the project's figure with the surgical team and the infection control officer.

Is NABH a design code for MEP systems?

No. NABH is an accreditation body that assesses hospital quality and safety against its own published standards. It does not replace the building code, electrical safety regulations or fire approvals. Designers use the government standards for numbers, then check the NABH edition current at the time of application for the processes the services must support, such as infection control and emergency power.

When is a medical gas pipeline system expected?

The district hospital standards say facilities with more than 50 beds would have a medical gas pipeline system supplying oxygen from a storage tank or generation plant to critical areas such as the operation theatre, labour room and emergency. The DGHS Hospital Manual asks for centralised piped gases including oxygen and suction in theatres, with alternate sources that are checked regularly.

What pressure and air change rate should an isolation room have?

The district hospital standards say isolation rooms should be separated from general wards, with negative air pressure and at least six air changes per hour. The number of isolation beds is tied to the hospital's bed count. Specific exhaust treatment and anteroom arrangements depend on the infection control assessment, so settle them with the clinical team before drawings are frozen.

What does power redundancy mean for a hospital?

It means critical loads keep running when the grid fails or a part of the electrical system is out. The public health standards expect uninterrupted electric supply for theatres and intensive care, and the 2026 building standards call for dedicated UPS and DG back-up for life-saving equipment on hospital refuge terraces. The design rarely stops there: separate feeders, automatic changeover and tested UPS runtime matter too.

Related services

Share the coordinated layouts or clash reports you have — an engineer reviews the services zones and where they conflict.

Services not fitting the drawings?

Tell us about your project — our engineers respond within one business day.

  • ★ 4.7 (230 Google reviews)
  • 535+ projects
  • Reply in 1 business day
Add details (optional — company, email, scope and site address)

🔒 Your details go straight to our team. No spam, ever.

Ready to start your project?

Get a free consultation and quote. We design, prepare and file your approvals, and execute — you deal with one team.

ONE PARTNER. END TO END. You focus on your business — we handle the rest.
Quality Safety Commitment
Speak to a Lead Engineer