LT panel contractor — PCC, MCC and APFC panels built to IEC 61439

Power and motor control centres, main and sub-distribution boards and automatic power-factor-correction panels, built to IEC 61439 with type-tested components.

Enquire: LT Panels — PCC / MCC / APFC

Step 1 of 3

What do you need?
What kind of facility?
Roughly how big is the project?
Where should our engineer call you?

No forms to chase — an engineer calls you back. We never share your number.

In one paragraph

LT Panels — PCC / MCC / APFC by Secured Engineers Pvt. Ltd.

Secured Engineers Pvt. Ltd. — an ISO 9001:2015-certified MEPF and solar EPC contractor with offices in Ludhiana, Punjab and Noida (Delhi NCR) — provides LT Panels — PCC / MCC / APFC as part of its Electrical scope: Power and motor control centres, main and sub-distribution boards and automatic power-factor-correction panels, built to IEC 61439 with type-tested components. 535+ projects across 18+ Indian states.

Enquiries: +91 70099 85817 · sales@securedengineers.com · request a project proposal

Why it matters

What this system decides for your project

Panels are the nerve centre of distribution. Type-tested designs and APFC keep the system safe, avoid penalty on power factor and reduce energy bills.

You need a quote for this if: New buildings, plant expansions or sites facing power-factor penalties.

Scope

Scope of work

Panels are designed from the single-line diagram — incomer and outgoing ratings, fault level, the form of internal separation the client's safety standard calls for, metering and protection relays, and the interlocks between incomers and bus couplers. Motor control centres carry the starters, drives and control logic the process needs; APFC panels are sized from the measured or calculated reactive demand, with detuned reactors where harmonics warrant them. We design the panels, have them built with type-tested components to approved makes, install them and terminate the cabling.

How it is delivered — and what you receive

Panels are inspected at the factory before dispatch and tested on site — insulation resistance, functional checks of every breaker, relay and interlock, and secondary injection of the protection relays. The APFC panel is commissioned against a live power-factor reading so the steps actually correct the load present. The client receives the general-arrangement drawings, the schematic, the relay settings and the test reports, which is also the record the CEIG inspection looks at.

Sources and standards

  • IS 732 (2019) — IS 732 — Code of Practice for Electrical Wiring Installations. Bureau of Indian Standards. Publisher.Low-voltage wiring installations — cable selection, protection, installation methods.
  • IS 3043 (2018) — IS 3043 — Code of Practice for Earthing. Bureau of Indian Standards. Publisher.Earthing system design, electrodes, resistance values and testing.
  • IEC 61439 — IEC 61439 — Low-voltage switchgear and controlgear assemblies. International Electrotechnical Commission. Publisher.Design verification and type-testing of LT panels — PCC, MCC, distribution boards.
  • CEA (Measures relating to Safety and Electric Supply) Regulations (2023 (superseding the 2010 regulations)) — Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations. Central Electricity Authority. Publisher.Safety requirements for electrical installations, inspection of HT installations before energisation, periodic inspection, earthing and protection.
  • NBC 2016 Part 8 (2016) — National Building Code of India 2016, Part 8 — Building Services. Bureau of Indian Standards. Publisher.Lighting, ventilation, air-conditioning, electrical installations, lifts and escalators — the building-services framework.

Standards are cited to support the technical statements on this page. Where a standard has been revised, the edition shown is the one verified at the time of review; the edition in force for a project is the one the authority applies.

Before you ask us to quote: the Electrical buyer's guide lists what to have ready, what drives cost and timeline, and the approvals that usually apply.

Approved makes

Makes we specify for LT Panels — PCC / MCC / APFC

Tier-1 manufacturers whose equipment we design around and install. The specification names the make; the site is held to it.

Schneider ABB Siemens L&T

Need LT Panels — PCC / MCC / APFC for your project?

Get a free consultation and quote. We design, take all approvals, and execute — you stay stress-free.